How to check Smoke Fan's for the Civil Defense Approval

How to Check Smoke Fans for Civil Defense Approval


Smoke fans are a critical part of a building’s fire safety system, designed to extract smoke and heat during a fire to maintain clear escape routes and assist firefighting efforts. For any building project, especially in regions like the Middle East, Civil Defense approval is mandatory before commissioning. Ensuring that smoke fans meet Civil Defense requirements involves both technical compliance and proper installation standards.


 Key Steps to Check Smoke Fans for Civil Defense Approval:

  1. Verify Product Certification:

    • Ensure the smoke fan has valid third-party certifications, such as EN 12101-3 or UL 705.

    • Check that the fan is rated for high-temperature operation, typically 300°C for 60 minutes or more.

    • Certifications should be from recognized testing bodies accepted by Civil Defense in your country.

  2. Check Manufacturer’s Documentation:

    • Obtain the technical datasheet, test reports, and declaration of conformity.

    • Ensure the fan model and performance match the approved fire safety design.

  3. Inspect Installation Quality:

    • Confirm that the fan is installed according to the manufacturer’s guidelines and local fire codes.

    • Mounting should include vibration isolators, fire-rated cabling, and secure duct connections.

    • All associated components (e.g., motorized dampers, control panels) should also be fire-rated and accessible.

  4. Electrical and Control Integration:

    • Verify that the fan is connected to the Fire Alarm Control Panel (FACP) or Building Management System (BMS).

    • Simulate a fire scenario to check automatic activation.

    • Ensure manual override controls are clearly labeled and accessible.

  5. Functional Testing and Commissioning:

    • Conduct on-site functional testing with Civil Defense or a third-party consultant present.

    • Record air volume (CFM), static pressure, and rotation direction to match design specifications.

    • Provide a test report and as-built documentation for final inspection.

  6. Maintenance and Access:

    • Check that the fan is accessible for maintenance, and filters or dampers (if present) are clean and operational.

    • Provide clear signage and access doors where required.


Getting smoke fans approved by Civil Defense requires careful attention to both product certification and field conditions. Always coordinate early with consultants and local authorities to ensure compliance. A properly selected and installed smoke fan not only meets legal requirements but also plays a vital role in saving lives during emergencies.